UNKNOWN113876

Substation-Adjacent

Franklin County, Ohio · PJM

DC Readiness
70.6
Excellent / 100

UNKNOWN113876 is a substation-adjacent datacenter candidate site in Franklin County, Ohio, interconnecting through PJM. It screens at 70.6/100 DC Readiness with a catalogued 100 MW of candidate capacity and a 3.2 yrs average interconnection-queue wait.

Power & interconnection

Nearest substationUNKNOWN113876
Substation distance0.0 mi
Substation voltage138 kV
Available capacity100 MW
LMP zonePJM_AEP
Wholesale LMP$41.99/MWh
Utility commercial rate0.13¢/kWh

Speed to power

ISO / RTO regionPJM
Queue depth9
Avg queue wait3.2 yrs
Recent queue wait4.4 yrs
Completion rate17%
Withdrawal rate83%

Connectivity

Nearest IXPBresco Broadband Data Center
IXP distance5.6 mi
Fiber providers17
Fiber coverage38.8%
Nearest cloud providerAWS
Nearest cloud regionus-east-2
Cloud region distance6.2 mi

Site characteristics

Parcel ownerUnited States Of America
Parcel APN090-001025
Land owner typeprivate
Buildability100.0/100
Land cover (NLCD)Developed, High Intensity

Risk & environment

Flood zoneZone X
Water stress (WRI)0.50
Wetlands (NWI)Clear
Critical habitatClear
Superfund nearbyPresent
Superfund siteAFP 85 JAMES ROAD HAZARDOUS WASTE PAD
Hazard sub-score60/100
Construction cost index109.6 (avg 100)

Location context

Nearest datacenterBresco Broadband Data Center
DC distance5.6 mi
Nearest rail0.1 mi
Nearest gas pipeline1.8 mi
Nearest fiber route24.8 mi
County hazard (FEMA NRI)Relatively Moderate (30)
DC tax incentiveYes (sales_tax_exemption)
Commercial electricity13.35¢/kWh
Industrial electricity9.95¢/kWh
Cooling degree days900
Heating degree days5,400
Land price / acre$11,462

Incentive detail: DC sales tax exemption on equipment and electricity (2022 law); JobsOhio grants.

Full DC Readiness breakdown

All 13 weighted sub-scores (0–100) behind the composite DC Readiness score.

Power availability20%
58
Speed to power15%
51
Fiber connectivity12%
82
Energy cost10%
84
Water risk8%
90
Natural hazard8%
60
Buildability7%
100
Labor market4%
50
DC cluster4%
95
Land / acreage3%
36
Construction cost3%
59
Gas pipeline2%
94
Tax incentive2%
100
Climate / cooling2%
80

Nearby comparable sites

Other scored datacenter candidate sites in Franklin County, ranked by DC Readiness.

Sites near UNKNOWN113876
SiteTypeVoltageCapacityQueue waitScore
HAYDENSubstation-Adjacent345 kV600 MW3.2 yrs77.3
UNKNOWN113629Substation-Adjacent345 kV600 MW3.2 yrs76.9
BEATTYSubstation-Adjacent345 kV600 MW3.2 yrs74.5
MARIONSubstation-Adjacent138 kV100 MW3.2 yrs71.8
DODGE PARK ENGINE NO 1Substation-Adjacent138 kV100 MW3.2 yrs71.7
UNKNOWN113866Substation-Adjacent138 kV100 MW3.2 yrs71.5
UNKNOWN141214Substation-Adjacent138 kV100 MW3.2 yrs71.5
UNKNOWN112899Substation-Adjacent138 kV100 MW3.2 yrs71.3

Dataset updated . Screening estimates derived from public data sources.

Figures are screening estimates derived from public infrastructure data. Catalogued capacity reflects theoretical candidate capacity, not deliverable or committed interconnection. Confirm all values with the utility, ISO, and on-the-ground due diligence.

Go deeper than the public screen